INSTRUMENTATION CABLES |
0.5 mm˛ TYPE : MULTI-PAIR SCREENED, OVERALL SCREENED
CONSTRUCTION
Conductor : Stranded Bare/Tinned Copper Wire
Insulation : Polyethelene(PE)or Poly Vinyl Chloride(PVC)
Nominal thickness : 0.4 mm
Dia.over insulation : 1.73 mm
Cores : Twisted pairs, 40-50 mm Colour Coded
Pair Screen : Polyester tape wrap
Solid/Stranded drain wire
Poly Al tape layer
Polyester tape layer
Communication Wires if necessary
Overall : Polyester Tape Wrap
Screen : Stranded Drain Wire 0.5mm˛
Poly – A1 Tape layer
Polyester Tape Layer
Outer sheath : PVC
NOTE: i) Similar construction for other conductor sizes like 0.75mm˛, 1.0mm˛, 1.5mm˛ and 2.5 mm2
ii) G.I. Wire Armouring and Outer sheath can be provided, where necessary.
BASIC SPECIFICATIONS AT 20
° C
Conductor Resistance : 38 Ohms/Km Max.
Insulation Resistance PE : 5000 M.Ohms.km.Min.
PVC : 100 M.Ohms.km.Min.
Mutual Capacitance at PE : 75 pF/Mtr.Max.
Hz (Core to Core) PVC : 140 pF/Mtr.Max.
Attenuation at 1 kHz PE : 1.3 dB/km.
PVC : 1.7 dB/Km.
Operating Voltage : 250 Volts.
| No. of Pairs | Laid-up dia. | Cables Wt. | Overall dia. |
| (approx.) | (approx.) | with armour & | |
| (mm) | kg/km. | Sheath (mm) | |
| 1 | 7.0 | 80 | 12.0 |
| 2 | 9.5 | 105 | 14.5 |
| 3 | 10.5 | 120 | 15.5 |
| 4 | 11.5 | 140 | 16.5 |
| 8 | 15.0 | 240 | 21.0 |
| 10 | 16.5 | 260 | 22.5 |
| 16 | 19.5 | 430 | 25.5 |
| 20 | 22.0 | 520 | 28.0 |
| 24 | 25.0 | 640 | 31.0 |